Air admittance valve pressure testing research
Historical specimen measurements, custom procedure and limits of interpretation.
Evidence and editorial policy
Two reports dated September 23, 2017, Lab 33972, identify one Studor Mini-Vent and one Sure-Vent specimen. The reports state that a client-supplied protocol was used. The supplied conversation reports a Tuuber comparison and odor experience, but no Tuuber report is available. Manufacturer-oriented articles are not independent validation. No named professional has endorsed this publication.
| Specimen | Negative upper/lower mbar | Positive upper/lower mbar |
|---|---|---|
| Studor | 2.5/1.61; 24.8/20.6; 37.8/31.2 | 2.3/2.31; 23.2/23.8; 33.8/34.1 |
| Sure-Vent | 2.5/2.31; 24.8/24.0; 37.2/35.8 | 2.5/2.53; 25.1/25.2; 38.4/38.2 |
Negative readings are interpreted as vacuum magnitudes. The positive test range in the supplied protocol differs from the report values. Pressure communication is not a direct gas measurement. No formal ASSE failure or brand-wide defect is established. The laboratory reports restrict use of its name without written approval; original report photos are excluded from the public build pending permission.
Calculated negative-pressure differences
| Specimen | Upper − lower magnitude (mbar) | Lower / upper magnitude |
|---|---|---|
| Studor | 0.89 | 64.4% |
| Studor | 4.20 | 83.1% |
| Studor | 6.60 | 82.5% |
| Sure-Vent | 0.19 | 92.4% |
| Sure-Vent | 0.80 | 96.8% |
| Sure-Vent | 1.40 | 96.2% |
What further testing should establish
Measure blank fixture leakage, signed pressures, time series, flow direction and tracer concentration. Use multiple specimens and realistic building pressure histories. The reported Tuuber result is not a numerical observation available for charting.
Source: supplied pressure differential reports dated September 23, 2017, reference 33972; supplied conversation and custom procedure. Original photographs and report reproductions are withheld pending permission.